7.2 Operating via AMS Device Manager
SITRANS LR250 (HART)
94 Operating Instructions, 01/2014, A5E32220602-AB
Using linearization via the Quick Start wizard
Navigate to
Configure/Setup > Wizard > Quick Start
.
In
Step 1 Identification,
make any desired modifications and click on
Apply
.
In
Step 2 Application,
select a level application and liquid as a material.
In
Step 3 Vessel Shape
, choose the vessel shape option
Linearization Table
.
In
Step 4 Ranges
, enter a value for maximum volume.
Breakpoints
Maximum volume
1. Click on the
Breakpoints
tab and enter values for level and volume for up to
32
breakpoints.
2. Navigate to
Configure/Setup > Setup > Linearization
and click on
Characteristic
to preview
the characteristic curve of the vessel breakpoints. (The conversion will function correctly even
if not all breakpoints are entered, but the curve will display correctly only if all breakpoints are
entered.)
3. In
Step 5 Summary
, check parameter values. Click on the appropriate step menu to return
and revise values, or click on a different menu to exit
Quick Start.