User's Manual
Table Of Contents
- SITRANS LR250 (HART)
- Legal information
- Table of contents
- 1 Introduction
- 2 Safety notes
- 3 Description
- 4 Installing/mounting
- 5 Connecting
- 6 Commissioning
- 7 Remote operation
- 7.1 Operating via SIMATIC PDM
- 7.1.1 Functions in SIMATIC PDM
- 7.1.2 Initial setup
- 7.1.3 Updating the Electronic Device Description (EDD)
- 7.1.4 Quick Start Wizard via SIMATIC PDM
- 7.1.5 Changing parameter settings using SIMATIC PDM
- 7.1.6 Parameters accessed via pull-down menus
- 7.1.6.1 Echo profile utilities
- 7.1.6.2 Echo profile
- 7.1.6.3 View saved echo profiles
- 7.1.6.4 TVT Shaper
- 7.1.6.5 Auto false echo suppression
- 7.1.6.6 Echo setup
- 7.1.6.7 Maintenance
- 7.1.6.8 Select analog output
- 7.1.6.9 Self test
- 7.1.6.10 Loop test
- 7.1.6.11 Configuration flag reset
- 7.1.6.12 Master reset
- 7.1.6.13 Wear
- 7.1.6.14 HART Communication
- 7.1.6.15 Process variables
- 7.1.6.16 Trend
- 7.1.6.17 Device status
- 7.1.6.18 Update
- 7.1.6.19 Security
- 7.2 Operating via AMS Device Manager
- 7.3 Operating via FDT (Field Device Tool)
- 7.1 Operating via SIMATIC PDM
Commissioning
6.2 Application examples
SITRANS LR250 (HART)
Operating Instructions, 01/2014, A5E32220602-AB
59
Propagation Factor/Stillpipe Diameter
①
sensor reference point
③
low calibration point
②
air gap
④
CLEF range 2.8.4.4.
A
700 or 1000 mm (see CLEF Range settings in table below)
Values
Range
0.3 to 1.0 depending on pipe size
Default
1.0000
Nominal Pipe Size
a)
40 mm (1.5")
50 mm (2")
80 mm (3")
100 mm (4")
Propagation Factor
0.9844
0.988
0.9935
0.9965
CLEF Range (2.8.4.4.) settings
Low
calibration
point -
700 mm
(2.29 ft)
b)
Low
calibration
point -
700 mm
(2.29 ft)
b)
Low calibration
point -1000 mm
(3.28 ft)
b)
Low calibration
point -1000 mm
(3.28 ft)
b)
a)
Since pipe dimensions may vary slightly, the propagation factor may also vary.
b)
CLEF range covers the whole measurement range except first 700 or 1000 mm from sensor
reference point
Note
Flanged encapsulated antenna
For Flange
d encapsulated antenna (7ML5432) match the process connection size to the
pipe diameter.
For example, DN 80/3" flange to DN 80/3" pipe.