6.2 Application examples
SITRANS LR250 (HART)
56 Operating Instructions, 01/2014, A5E32220602-AB
Parameter type
Parameter No./Name
Options/
Values
Function
High Calibration Point
0.5
0.5 m (1.64 ft)
Wizard Complete
FINISH
Transfers Quick Start
settings to device.
Independent
parameters
Vessel Shape (2.7.1.1.)
PARABOLIC
ENDS
Defines vessel shape.
Maximum Volume (2.7.1.2.)
8000
8000 liters
Vessel Dimension A (2.7.1.3.)
0.8
0.8 m (2.62 ft)
Vessel Dimension L (2.7.1.4.)
6
6 m (19.68 ft)
LOE Timer (2.5.2.)
2
2 minutes
Material Level (2.5.1.)
HI
Fail-safe level set to High
Return to
Measurement:
press
Mode
to start normal operation.