User's Manual
Page EN-8 SITRANS LR 200 – QUICK START MANUAL 7ML19985QL81
mmmmm
English
Master Reset (P999)
Returns all parameters to default settings.
1. Press PROGRAM
,
then DISPLAY to activate PROGRAM mode.
2. Press DISPLAY to open parameter fields.
3. Key in 999.
4. Press CLEAR
then
ENTER , to Clear All
and initiate reset. The LCD displays C.ALL.
5. Reset complete. (Reset takes several seconds
to complete.
Quick Setup: steps 1 to 9
1. Select language (P010: Language)
2. Set P001: Operation (measurement mode)
Value
0*
Numeric/None
1
English
2
German
3
French
4
Spanish
Notes:
• Setting P001 resets Span (P007), unless Span has previously been set to a different value.
• Changing P001 may reset Output Function (P201): this applies to HART only.
Value
0
Instrument out of service.
1
Level returns distance to material level referenced from Empty (process empty level). The
reading is returned in volumetric units if parameters 050 to 055 are set to enable this.
2
Space returns distance to material level referenced from Span (process full level).
3*
Distance returns distance to material level from reference point.
Level
(P001 = 1)
Space
(P001 = 2)
Distance
(P001 = 3)
Distance
Space
Level
P007
P006
100%
(20 mA)
(20 mA)
100%
0%
(4 mA)
(4 mA)
0%
100%
(20 mA)
(4 mA)
0%
Empty
Span
Span
Empty
Span
Empty
mA Output with Level, Space, and Distance operation
LR-200QS-EN.fm Page 8 Wednesday, March 12, 2003 3:51 PM
corrected