User's Manual

7ML19985QL81 SITRANS LR 200 – QUICK START MANUAL Page EN-7
mmmmm
English
Activating SITRANS LR 200
Power up the instrument. SITRANS LR 200 starts in RUN mode.
Accessing a parameter
1. Press PROGRAM then DISPLAY , to
activate PROGRAM mode.
2. Either use the ARROW keys to scroll to a
different parameter, or:
3. Press DISPLAY
to open the Parameter
Number field.
4. Key in the desired parameter number followed by
ENTER .
For example: press
.
The LCD displays the new parameter number and
value.
Changing a Parameter Value
1. Key in the new value.
2. Press ENTER to set the value.
Parameter Reset to Factory Default
1. Scroll to the parameter or enter its address.
2. Press CLEAR
then ENTER . The value returns to the default setting.
Notes:
Press PROGRAM
then DISPLAY to access PROGRAM mode, and press
PROGRAM to return to RUN mode.
The following instructions apply when using the Hand Programmer
You do not need to key in initial zeros when entering a parameter number: for
example, for P005, key in 5.
Notes:
Security must be disabled to enable programming: set P000 to the Unlocked Value
stored in P069. (A remote master can still change configuration, if P799 is set to
allow this.)
Invalid entries will be rejected or limited.
CLEAR can be used to clear the field.
Parameter Value
Parameter Number
PROGRAM Icon
current value
LR-200QS-EN.fm Page 7 Wednesday, March 12, 2003 3:51 PM