User's Manual

Page EN-4 SITRANS LR 200 – QUICK START MANUAL 7ML19985QL81
mmmmm
English
Avoid central locations on vessels
s.
Wiring
Power
Connecting SITRANS LR 200
1
Use the 100 mm (4") shield on nozzles that are 100 mm (4") in length, or shorter.
Use the 250 mm (10") shield on nozzles that are 250 mm (10") in length, or shorter.
WARNINGS:
dc terminals shall be supplied from an SELV source in accordance with
IEC-1010-1 Annex H.
All field wiring must have insulation suitable for rated input voltages.
Notes:
For complete wiring instructions, please refer to the Instruction Manual.
Use shielded, twisted pair cable (wire gauge 14-22).
Separate cables and conduits
1
may be required to conform to standard instrumentation
wiring practices, or electrical codes.
1.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof application.
preferred undesirable
Coni
Fl at
Flat Parabolic Conical
m
i
n. 300 mm
(
1
’)
f
or every
3 m (10’) of vessel height.
beam
angle
20
o
locate the antenna away from the side wall, to
avoid interference from indirect echoes
avoid interference from objects such as
ladders or pipes, which can cause false
reflections
minimum
100 mm (4")
To provide optimum signal conditions on a manhole cover, locate
the antenna off-center relative to the cover, typically 100 mm
(4”) from the side of the manhole
minimum
10 mm (0.4")