User's Manual

Table Of Contents
PL-611 IQ Radar 300 Page 83
Communications
Communications
Communications
Communications
Format Word (R43,997)
Format word is an unsigned integer that contains a value that represents a certain
decimal offset.
The decimal offset indicates how the remote system must interpret the integer value
that is stored in the parameter access register. The following table shows how different
parameter values can be shown based on a register value (integer) of 1234.
Decimal Offset Example
0 0 1,234
1 -1 12,340
2 -2 123,400
3 -3 1,234,000
4 -4 12,340,000
5 -5 123,400,000
6 +1 123.4
7 +2 12.34
8 +3 1.234
9 Percent 12.34%
Examples of using the format word for both the index values and the decimal offset
value are shown below:
Format Decimal
00
3 3 right
8 3 left
9percent
Primary Index (P43,999) and Secondary Index
(P43,998)
Many parameters are indexed. There are two possible indexes, a primary index and a
secondary index. If there is not an index, enter a value of 1
11
1.
Reading Parameters
To read parameter values, follow the steps listed in either the Global or the Parameter
Specific Index Method that follow. You must be able to program your HMI or SCADA
system before completing these methods.
1. Write the primary index value into R43,999.