User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
Page 82 IQ Radar 300 PL-611
Communications
Communications
Communications
Communications
The measurement registers is 41,010.
The available register
Data Registers Parameter
Reading 41,010 P920
Volume 41,020 P924
Temperature 41,030 and 41,031 P912
The reading is expressed as a percentage of full scale, multiplied by 100:
Reading Value
0 0.00%
5000 50.00%
7564 75.64%
20,000 200.00%
Input/Output (R41,070 – R41,143)
The IQ 300 has one mA output.
mA Output (R41,110)
The mA output is scaled from 0 to 2,000 (0 to 20mA multiplied by 100). Displayed in P911.
Parameter Access (R43,997 – R46,999)
Parameter values are given as integers in the range of registers from R44,000 to R44,999.
The last three numbers of the register correspond to the parameter number.
Parameter Register # Format Register # Parameter #
44,000 46,000 P000
44,001 46,001 P001
44,002 46002 P002
………
44,999 46,999 P999
The parameters are usually all read/write.
Note:
• Parameters P000 and P999 are read only. If P000 is set to LOCK ON then all of
the parameters are read only.
• Parameter P999 (Master Reset) cannot be used via Modbus.
• See Data Types on page 85 for a description of the different types of data
associated with different parameters.
However, before a parameter can be read or written to, the format (where decimal place
is) and the indexes must be defined.