User's Manual

Table Of Contents
Page 78 IQ Radar 300 PL-611
Parameters
Parameters
Parameters
Parameters
Use this feature to adjust the slope declination, and use it in conjunction with TVT Start
Duration (when a long flat TVT Type is selected) to ensure the TVT Curve remains above
the false echoes in the middle of the Echo Profile. Alternatively, if TVT Type is set for TVT
TVTTVT
TVT
Slopes
SlopesSlopes
Slopes (P830 = 6), pre-set is 2000.
P837 Auto Near TVT
Use this feature to adjust the TVT Curve height to ignore false echoes near the start of
the Echo Profile by placing the TVT above the current signal from 0m to 2m (78).
If the IQ 300 displays a full level, or if the reading fluctuates between a high level and a
correct level, set this parameter to elevate the TVT in this region and to de-sensitize the
receiver from any base noise caused by internal antenna reflections and/or standpipe
echoes.
Entry:
0 = Off (not used)
1 = Use Learned TVT
2 = Learn
Set Up:
1. Make sure material is at least 2.5m (78) away.
2. Press the PROGRAM key
, press the TOGGLE
key
, and then select P833.
3. Press 2 and then press the ENTER key
.
4. Press 1 and then press the ENTER key
.
Press the PROGRAM key
to return to RUN mode.
Test Parameters
P900 Software Revision
Displays the EPROM software revision level.
Values (view only) Range: 00.00 to 99.99
P901 Memory
Tests the memory. Test is initiated by scrolling to the parameter or repeated by pressing
the ENTER key .
PASS
normal
Values (view only)
FAIL
consult Milltronics