User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
PL-611 IQ Radar 300 Page 77
Parameters
Parameters
Parameters
Parameters
breakpoints, the effective bias to the shaper can be broadened to suit the desired
correction. In the case of multiple false echoes, shaping can be applied along different
points of the curve. Shaping should be applied sparingly in order to avoid missing the
true echo.
To change a breakpoint:
1. Confirm that P831, TVT shaper, is ON.
2. Go to P832
3. Press
twice to highlight the index value
4. Press
or to scroll through the 40 points (or type in the desired point)
5. Enter the value from –50 to 50
6. Press
P833 TVT Start Min
Use this feature to adjust the TVT Curve height to ignore false echoes (or pick up true
echoes) near the start of the Echo Profile.
Range: 30 to 225
Values
Pre-set: 50
Related Parameters
• P834 TVT Start Duration
Enter the minimum TVT Curve start point (in dB above 1 uV RMS).
This feature should only be used if increased Near Blanking (P800) would extend farther
than desired into the measurement range.
P834 TVT Start Duration
Use this feature in conjunction with TVT Start Min (P833) to ignore false echoes (or pick
up true echoes) near the start of the Echo Profile.
Range: 0 to 9999
Values
Pre-set: 30
Related Parameters
• P833 TVT Start Min
• P835 TVT Slope Min 77
Enter the time (in ms) for the TVT Curve to decrease from the TVT Start Min (P833) point
to the TVT Curve baseline.
P835 TVT Slope Min
Enter the minimum slope (in dB/s) for the middle of the TVT Curve.
Range: 0 to 9999
Values
Pre-set: 200
Related
• P834 TVT Start Duration