User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
Page 74 IQ Radar 300 PL-611
Parameters
Parameters
Parameters
Parameters
Note: P000 and P799 are exclusive, but locks can be implemented in different ways.
• HART lock device command sets P000 to a locked value and sets P799 to 2
• The hand programmer retains control if P000 is set to UNLOCK.
Echo Processing Parameters
P800 Near Blanking
Sets the amount of blanking as measured from the flange face and extending into the
measurement range. See Blanking on page 46.
Range: 0 to 9999
Values
Pre-set: 0.4m
Enter value in units of P005.
Note:
::
: This parameter may be set at the factory. If so, the appropriate values appear
on the product tag.
P801 Range Extension
Sets the amount of range extension as measured from the empty distance (P006) and
extending into the far-end blanking. See Blanking on page 46.
Range: 0 to 99%
Values
Pre-set: 5%
Enter value as a % of P006. The distance below empty is not blanked.
For tanks with conical or parabolic bottoms, increase this parameter to ensure that an
empty tank reads empty.
P804 Confidence Threshold
Sets the minimum echo confidence in dB that the echo must meet in order to prevent a
loss of echo condition and the expiration of the fail-safe timer (P070).
Range: 0 to 99
Values
Pre-set: 5
Related Parameters
• P070 Fail-Safe Timer
P805 Echo Confidence
Measures echo reliability.
Values (view only) Display: 0 to 99