User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
Page 70 IQ Radar 300 PL-611
Parameters
Parameters
Parameters
Parameters
P705 Rate Update Time
Sets the time period (in seconds) over which the material level rate of change is
averaged before Rate Value update.
Values Range: 0.000 to 9999
Related Parameter
• P707 Rate Value
P706 Rate Update Distance
The material level change (in metres) to initiate a Rate Value update.
Values Range: 0.000 to 9999
Related Parameter
• P707 Rate Value
P707 Rate Value
The rate of material level change (in Units (P005) or % of Span (P007) per minute).
Values (view only) Display: -999 to 9999
Altered By
• P704 Rate Filler
Related Parameters
• P005 Units
• P007 Span
A negative rate indicates the vessel is emptying.
Measurement Verification Parameters
P710 Fuzz Filter
Stabilizes the reported level due to level fluctuations (such as a rippling or splashing
liquid surface) within the Echo Lock Window (P713).
Values Range: 0 to 100 (0= off)
Altered by
• P003 Measurement Response
Related Parameters
• P007 Span
• P713 Echo Lock Window
This value (in % of Span, P007) is automatically altered when Measurement Response
Speed (P003) changes. The higher the value entered, the greater the range of stabilized
fluctuation.