User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
PL-611 IQ Radar 300 Page 69
Parameters
Parameters
Parameters
Parameters
P003 Value Meters/Minute
10.1
21
310
4 100
5 1000
P701 Maximum Empty Rate
Adjusts the IQ 300 response to decreases in the actual material level (or an advance to a
lower Failsafe Material Level, P071).
Values
ValuesValues
Values
Range: 0.000 to 9999 (stored in meters)
Altered by
Altered byAltered by
Altered by
• P003 Measurement Response
Related Parameters
Related ParametersRelated Parameters
Related Parameters
• P005 Units
• P007 Span
• P071 Fail-Safe Material Level
Enter a value slightly greater than the vessel’s maximum emptying rate. This value, in
Units (P005) or % of Span (P007) per minute, is automatically altered when Measurement
Response Speed (P003) is altered. Any emptying rate above this value will trigger any
alarms set to Rate.
P003 Value Meters/Minute
10.1
21
310
4 100
5 1000
P704 Rate Filter
Damps Rate Value (P707) fluctuations.
0
rate display not required
1
continuously filtered and updated
Values
2
update rate (use P705/P706)
Alters
• P707 Rate Value
Related Parameters
• P705 Rate Update Time
• P706 Rate Update Distance
Enter the time or distance interval over which the Rate Value is to be calculated before
the display updates.
This is automatically altered along with Measurement Response Speed (P003).