User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
Page 68 IQ Radar 300 PL-611
Parameters
Parameters
Parameters
Parameters
Pipe Size (i.d.) Propagation Factor
50mm (2”) 0.827
80mm (3”) 0.915
100mm (4”) 0.955
150mm (6”) 0.980
20 mm (8”) 0.990
Consult the factory for other sizes and propagation factor numbers.[Tim: who at the
factory?]
Note:
: :
: For waveguide antennas used as stillpipes, this value is on the product tag.
The propagation factor is constant for a given
pipe diameter,
or can be determined by
comparing the radar distance reading to the
actual process material distance (measured
from the face of the IQ 300 flange).
actual distance
= p.f.
IQ 300 distance
Using the readings shown:
10.42m
= 0.827
12.6m
Enter the propagation factor: 0.827
0.8270.827
0.827
Rate Parameters
These parameters determine how material level changes are reported.
P700 Maximum Fill Rate
Adjusts the IQ 300 response to increases in the actual material level (or an advance to a
higher Failsafe Material Level, P071).
Values
ValuesValues
Values
Range: 0.000 to 9999 (stored in meters)
Altered by
Altered byAltered by
Altered by
• P003 Measurement Response
Related Parameters
Related ParametersRelated Parameters
Related Parameters
• P005 Units
• P007 Span
• P071 Fail-Safe Material Level
Enter a value slightly greater than the maximum vessel filling rate. This value, in Units
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process
Speed (P003) is altered.