User's Manual

Table Of Contents
PL-611 IQ Radar 300 Page 67
Parameters
Parameters
Parameters
Parameters
If the level changes at a greater rate than the corresponding Filling/Emptying Indicator
(P702/P703) values, the Echo Profile is saved subject to this and other Auto Profile
Record restrictions.
P337 Auto Record LOE Time
Limits Auto Profile Records from being saved unless extended LOE occurs.
Range: 0.0 to 9999
(seconds)
Values
Pre-set: 0.0
Related Parameters
P334 Auto Record ON
P335 Auto Record OFF
P336 Auto Record Filling/Emptying
If the LOE condition exceeds the period entered the Echo Profile is saved. When set for 0
0 0
0
(zero) LOE is not required for an Auto Profile Record to be saved.
Installation Records Parameter
P341 Run Time
Shows the accumulated number of days the IQ Radar 300 has been operating.
Values (view only) Display:
0.0 to 9999 (days)
Range Calibration Parameters
P652 Offset Correction
Shows the offset value applied to the reading as a correction to the measurement.
Range:
-999 to 9999
Values
Pre-set: 0
Note: This parameter is automatically set when you enter parameter P004. This parameter may
also have been factory set to a specific value to accommodate options such as horn and
waveguide antenna systems. A tag on the instrument will specify the P652 value when these
options have been supplied.
P655 Propagation Factor
Compensates for the change in the microwave velocity, as compared with propagation
in free space, when propagation is within a stillpipe (metal).
Range:
0.000 to 1.000
Values
Pre-set: 1