User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
Page 66 IQ Radar 300 PL-611
Parameters
Parameters
Parameters
Parameters
Range:
0.0 to 9999
(minutes)
Values
Pre-set: 120 minutes
Auto Record ON and OFF Setpoint Parameters (P334 to
P337)
Use Auto Record ON Setpoint (P334) and Auto Record OFF Setpoint (P335) to define the
level boundaries that trigger an Auto Profile Record of an Echo Profile.
If ---- is displayed for either P334 or P335, Auto Profile Records are saved, regardless of
current level (subject to all other restrictions).
Enter the level value in Units (P005) or percent of Span (P007) relative to Empty (P006).
P334 Auto Record ON Setpoint
Sets the critical level which, along with Auto Record OFF
OFFOFF
OFF Setpoint, defines the
boundaries for Auto Profile Records to be saved.
Values Range:
-999 to 9999
Related Parameters
• P335 Auto Record OFF
• P336 Auto Record Filling/Emptying
• P337 Auto Record LOE Time
P335 Auto Record OFF Setpoint
Sets the critical level which, along with Auto Record ON
ONON
ON Setpoint, defines the
boundaries for Auto Profile Records to be saved.
Values Range:
-999 to 9999
Related Parameters
• P334 Auto Record ON
• P336 Auto Record Filling/Emptying
• P337 Auto Record LOE Time
P336 Auto Record Filling/Emptying
Restricts Auto Profile Records from being saved unless the level is rising, falling, or both.
0
Auto Profile Record on filling or emptying
1
Auto Profile Record on filling only
Values
2
Auto Profile Record on emptying only
Related Parameters
• P334 Auto Record ON
• P335 Auto Record OFF
• P337 Auto Record LOE Time
• P702 Filling Indicator
• P703 Emptying Indicator