Page 66 IQ Radar 300 PL-611
Parameters
Parameters
Parameters
Parameters
Range:
0.0 to 9999
(minutes)
Values
Pre-set: 120 minutes
Auto Record ON and OFF Setpoint Parameters (P334 to
P337)
Use Auto Record ON Setpoint (P334) and Auto Record OFF Setpoint (P335) to define the
level boundaries that trigger an Auto Profile Record of an Echo Profile.
If ---- is displayed for either P334 or P335, Auto Profile Records are saved, regardless of
current level (subject to all other restrictions).
Enter the level value in Units (P005) or percent of Span (P007) relative to Empty (P006).
P334 Auto Record ON Setpoint
Sets the critical level which, along with Auto Record OFF
OFFOFF
OFF Setpoint, defines the
boundaries for Auto Profile Records to be saved.
Values Range:
-999 to 9999
Related Parameters
P335 Auto Record OFF
P336 Auto Record Filling/Emptying
P337 Auto Record LOE Time
P335 Auto Record OFF Setpoint
Sets the critical level which, along with Auto Record ON
ONON
ON Setpoint, defines the
boundaries for Auto Profile Records to be saved.
Values Range:
-999 to 9999
Related Parameters
P334 Auto Record ON
P336 Auto Record Filling/Emptying
P337 Auto Record LOE Time
P336 Auto Record Filling/Emptying
Restricts Auto Profile Records from being saved unless the level is rising, falling, or both.
0
Auto Profile Record on filling or emptying
1
Auto Profile Record on filling only
Values
2
Auto Profile Record on emptying only
Related Parameters
P334 Auto Record ON
P335 Auto Record OFF
P337 Auto Record LOE Time
P702 Filling Indicator
P703 Emptying Indicator