User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
PL-611 IQ Radar 300 Page 65
Parameters
Parameters
Parameters
Parameters
P330 Profile Record.
Records profiles for later viewing.
In addition to being a profile records library, this provides two functions:
• manually records and saves echo profiles
• displays an echo profile, recorded manually or automatically, (oscilloscope)
Selecting a record address
1. Enter PROGRAM mode and press TOGGLE key twice to highlight the index field. The
field shows two underscores _ _
_ __ _
_ _.
2. Type the index number. The profile record information is shown.
3. Use ARROW keys
and to scroll through the records.
Recording a profile manually
Press the TRANSDUCER key to fire the transducer and record the echo profile into
the internal scope buffer for display.
Saving a manual record
Press the ENTER key to copy the echo profile record in the scope buffer and save it
in the selected address in the record library. The parameter value field displays the new
record information.
Displaying a record
Press the AUXILIARY key to enter display auxiliary mode and then:
1. Press
to display the time the profile was taken.
2. Press
to display the date the profile was taken.
3. Press the TRANSDUCER key
to copy the current echo profile into the scope buffer
for display on an oscilloscope or in Dolphin Plus.
To delete a record
Press the CANCEL key and then the ENTER key to delete the echo profile
record in the selected address. The value returns to - - - -
- - - -- - - -
- - - -.
P331 Auto Record Enable
Enables or disables the Auto Profile Record function.
0
Off
Values
1
On
P333 Auto Record Interval
Sets the allowable time lapse (in minutes) after an Auto Profile Record is saved before
another Auto Profile Record can be saved (subject to all other restrictions).