User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
Page 64 IQ Radar 300 PL-611
Parameters
Parameters
Parameters
Parameters
P214 mA Trim
Used to calibrate the mA output for 4mA.
Values Range: -1.00 to 1.000
Related Parameters
• P215 mA Trim
Adjust this value so the input device indicates 4.000mA when P214 is accessed. Clearing
this parameter returns unit to factory setting.
P215 mA Trim
Used to calibrate the output for 20 mA.
Values Range: -1.00 to 1.000
Related Parameters
• P214 mA Trim
Adjust this value so the device indicates 20.00mA when P215 is accessed. Clearing this
parameter returns unit to factory setting.
P219 mA Output Fail-Safe
Use for mA fail-safe operation, independent of the Fail-Safe Material Level (P071).
0 Off (pre-set) mA output responds to Failsafe Material Level
1 HI produce the Span mA output immediately
2 LO produce the Empty mA output immediately
Values
3HOLd
last known value is held until normal operation
resumes
Profile Record Parameters (P330 to P337)
WARNING: These parameters are for authorized service personnel or
Technicians familiar with Milltronics echo processing techniques.
These features can record up to 10 Echo profiles, initiated manually (P330), or
automatically (P331). See Scope displays (P810) for echo profile viewing
hardware/software requirements. If 10 Profiles are already saved, addresses 1 through
10 are filled, and the oldest automatically initiated record is overwritten. Manually
initiated records are not automatically overwritten. All records are automatically deleted
in the event of a power interruption.
When a record is displayed, results are based on current programming (which may have
been altered since the record was saved), so the effect on the echo profile can be
observed when changing an echo parameter.