P201 mA Function
Alters the mA output/measurement relationship. Set independently from P001.
0 manual
1 level
2 space
3
distance
4
volume
Values
9
controlled by HART or Modbus
Independent mA Setpoints Parameters (P210 and P211)
Use these features as reference for calculating the minimum and/or maximum mA
output to any point in the measurement range.
Note: Ensure the % symbol is displayed before entering a % value.
P201 (mA Function) Settings Response
level, space, or distance
Enter the material level in Units (P005) or percent of Span
(P007) as referenced to Empty (P006).
volume
Enter the volume in Maximum Volume (P051) units or as a
percent of Maximum Volume.
P210 0/4mA Output Setpoint
Sets the process level that corresponds to the 0 or 4mA value.
Values Range: -999 to 9999
Related
Parameters
P200 mA Range
P201 mA Function
Enter the value (in units or %) to correspond to 0 or 4mA.
P211 20mA Setpoint
Sets the process level that corresponds to the 20mA value.
Values Range: -999 to 9999
Related Parameters
P200 mA Range
P201 mA Function
Enter the value (in applicable units or %) to correspond to 20mA.