P070 Fail-Safe Timer
Sets the time delay, in minutes, before going into fail-safe mode.
Range:
: :
: 0.000 to 9999
Values
Pre-set: 10.00 minutes
P071 Fail-Safe Material Level
Selects the default measurement in the event that the fail-safe timer expires.
1 High: maximum span value
2 Low: minimum span value
Values
3 Hold: hold current value
P072 Fail-Safe Level Advance
Sets the speed at which the IQ 300 advances and returns to the Failsafe Material Level.
1
Restricted (pre-set): unit advances to/from the Failsafe Material lev
e
as set by P003, P700, or P701.
2 Immediate: Failsafe Material Level is assumed at once.Values
3
Fast Back: Failsafe Level Advance is restricted. Returns to new
measured material level at once.
mA Parameters (P200 to P219)
P200 mA Range
Selects the mA output range and relationship to span.
2
4 to 20mA
Values
4
20 to 4mA
If 2 is selected, the mA output is directly proportional to the mA function. If 4 is selected,
then the output is inversely proportional to the mA function.