User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
Page 62 IQ Radar 300 PL-611
Parameters
Parameters
Parameters
Parameters
Fail-Safe Parameters (P070 to P072)
P070 Fail-Safe Timer
Sets the time delay, in minutes, before going into fail-safe mode.
Range:
: :
: 0.000 to 9999
Values
Pre-set: 10.00 minutes
P071 Fail-Safe Material Level
Selects the default measurement in the event that the fail-safe timer expires.
1 High: maximum span value
2 Low: minimum span value
Values
3 Hold: hold current value
P072 Fail-Safe Level Advance
Sets the speed at which the IQ 300 advances and returns to the Failsafe Material Level.
1
Restricted (pre-set): unit advances to/from the Failsafe Material lev
e
as set by P003, P700, or P701.
2 Immediate: Failsafe Material Level is assumed at once.Values
3
Fast Back: Failsafe Level Advance is restricted. Returns to new
measured material level at once.
mA Parameters (P200 to P219)
P200 mA Range
Selects the mA output range and relationship to span.
2
4 to 20mA
Values
4
20 to 4mA
If 2 is selected, the mA output is directly proportional to the mA function. If 4 is selected,
then the output is inversely proportional to the mA function.