User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
PL-611 IQ Radar 300 Page 61
Parameters
Parameters
Parameters
Parameters
Display and Reading Parameters (P060 to P063)
P060 Decimal Position
Defines the maximum number of decimal places used on the LCD.
0
no digits after the decimal point
1
1 digit after the decimal point
2
2 digits after the decimal point
Values (Level
measurement only)
3
3 digits after the decimal point
In the RUN
RUNRUN
RUN mode, the decimal position is adjusted to prevent the number of digits from
exceeding the display capabilities. To keep the decimal place from shifting, reduce the
number of decimal places to that shown at 100%.
For example, if 100% = 15m, use two decimal places for readings of 15.00 or parts
thereof (e.g. 12.25).
P062 Offset Reading
Adds the specified value to the level reading, usually to reference the reading to sea
level or to another datum level.
Range:
-999 to 9999
Values (
Values (Values (
Values (Level
measurement only)
measurement only)measurement only)
measurement only)
Pre-set: 0.000
The operation of the device is not affected by the Offset Reading. This value is used for
display only. All control measurements are still referenced to empty.
P063 Minimum Reading
Adjusts the minimum reading the product will show.
Range:
-999 to 9999
Values (
Values (Values (
Values (Level
measurement only)
measurement only)measurement only)
measurement only)
Pre-set: 0.000
P063 is only applied after P062 Offset Reading and then only if reading displays
level/volume (P001=1).
The milliAmp output is not affected.