PL-611 IQ Radar 300 Page 61
Parameters
Parameters
Parameters
Parameters
Display and Reading Parameters (P060 to P063)
P060 Decimal Position
Defines the maximum number of decimal places used on the LCD.
0
no digits after the decimal point
1
1 digit after the decimal point
2
2 digits after the decimal point
Values (Level
measurement only)
3
3 digits after the decimal point
In the RUN
RUNRUN
RUN mode, the decimal position is adjusted to prevent the number of digits from
exceeding the display capabilities. To keep the decimal place from shifting, reduce the
number of decimal places to that shown at 100%.
For example, if 100% = 15m, use two decimal places for readings of 15.00 or parts
thereof (e.g. 12.25).
P062 Offset Reading
Adds the specified value to the level reading, usually to reference the reading to sea
level or to another datum level.
Range:
-999 to 9999
Values (
Values (Values (
Values (Level
measurement only)
measurement only)measurement only)
measurement only)
Pre-set: 0.000
The operation of the device is not affected by the Offset Reading. This value is used for
display only. All control measurements are still referenced to empty.
P063 Minimum Reading
Adjusts the minimum reading the product will show.
Range:
-999 to 9999
Values (
Values (Values (
Values (Level
measurement only)
measurement only)measurement only)
measurement only)
Pre-set: 0.000
P063 is only applied after P062 Offset Reading and then only if reading displays
level/volume (P001=1).
The milliAmp output is not affected.