User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
Page 60 IQ Radar 300 PL-611
Parameters
Parameters
Parameters
Parameters
P054 Breakpoint Levels
When the tank shape is too complex for any of the pre-configured shapes, you can
specify the volume based on segment.
Primary Index
global
Secondary Index
breakpoint
Values Range:
0.000 to 9999
in units
Related Parameters
• P055 Volume Breakpoints (Universal Volume Calculation)
Enter up to 10 level breakpoints (where volume is known) if P050 = 9 [verify]
Entering a Level Breakpoint
1. Open parameter P054.
2. Enter a breakpoint in measurement units.
3. Match each breakpoint to the same index value for P055.
P055 Volume Breakpoints (Universal Volume Calculation)
Each segment defined by the level breakpoints (P055) requires a volume to allow the IQ
300 to make the level-to-volume calculations.
Primary Index
global
Secondary Index
breakpoint
Range:
0.
..
.000 to
to to
to 9999
in units
Values
Pre-set: 0.000
Related Parameters
• P054 Volume Breakpoints (Universal Volume Calculation)
Typical volume calculations:
Cone Cylinder
V = (1/3)πr
2
hV = πr
2
h
Entering a Volume Breakpoint
1. Open parameter P055
2. For each index enter a volume
3. Match each volume to the same index value for P054