User's Manual

Table Of Contents
PL-611 IQ Radar 300 Page 59
Parameters
Parameters
Parameters
Parameters
P051 Max Volume
For Readings in volumetric units (rather than percent), enter the vessel volume between
Empty (P006) and Span (P007).
Values Range:
0.000 to 9999
Related Parameters
P006 Empty
P007 Span
The units of measurement for this reading are non-dimensional. The volume is
calculated from the empty position to the maximum position and is scaled according to
the Tank Shape (P050) value. This allows the use of any volume units required.
Example
1. If maximum volume = 3650m
3
, enter 3650
36503650
3650.
2. If maximum volume = 267500 gallons, enter 267.5
267.5267.5
267.5 (1000s of gallons).
Enter the volume of the tank at full (Factory Setting = 100)
P052 Tank Dimension A
Dimension A is used in the tank shape parameter (P050) on page 57.
Values
Range: 0.000 to 9999
0.000 to 9999 0.000 to 9999
0.000 to 9999 in units (P005)
))
)
Related Parameters
P050 Tank Shape
If P050 = 2,3,4, or 5, enter the height of the tank bottom.
If P050 = 7, enter the length of one end section of the tank.
Note: Enter the dimension in units chosen in (P005).
P053 Tank Dimension L
Dimension L is used in the tank shape parameter (P050) on page 57.
Values Range:
: :
: 0.000 to 9999
in units (P005)
Related Parameters
P050 Tank Shape
If P050 = 7, enter the tank length (excluding both end sections).
Note: Enter the dimension in units chosen in (P005).