Parameters
Parameters
Parameters
Parameters
P005 Units
Specifies units for programming and measurement.
1
metres
2
centimetres
3
millimetres
4
feet
Values
5
inches
P006 Empty
Sets the distance in units (see P005) from flange face
to empty level.
Values -----
# units set in P005
Empty level can be set at any distance
desired, not just actual empty.
P007 Span
Sets the distance from empty (P006) to full/100% level.
Values -----
# units set in P005
Full level can be set at any measurement
above the empty level.
Volume Parameters (P050 to P053)
Sets the IQ Radar 300 to calculate readings based on reservoir volume, rather than level
P050 Tank Shape
Enter the Tank Shape value that matches the monitored vessel or reservoir.
When Operation is LEVEL
LEVELLEVEL
LEVEL (P001 = 1), liquid (material) volume is calculated. When
operation is SPACE
SPACESPACE
SPACE, remaining vessel capacity is calculated.
In the RUN
RUNRUN
RUN
mode, Readings are displayed in volumetric units, see Maximum Volume
(P051) on page 59. When percent is selected, the displayed volume Reading is a
percentage of Maximum Volume.
Note: Parameters P052 and P053 set tank dimensions A and L.