P002 Material
Identifies the material being monitored.
Values 1
liquids or slurries
P003 Measurement Response
Sets the reaction speed of the unit to the measurement changes in the target range.
measurement
response
P700/P701
rate
update
time
P705
rate
update
distance
P706
fuzz
filter
P710
echo
verification
P711
fail
safe
timer
P070
1 0.1m/minute slow
600 secs 0.30 m
2100100
2 1m/minute
300 secs 0.10m
25010
3 10m/minute
60secs 0.05m
2101
4 102m/minute
60secs 0.05m
010.1
Values
5 1020m/minute fast
60secs 0.05m
000
Set P003 to a measurement response just faster than the greater measurement of the
maximum filling or emptying rate.
If the IQ 300 cannot keep up with the rate of level change, select a faster rate. If the
reading bounces around an average value, select a slower rate. In general, reliability is
traded for speed. Noisy applications or those with agitators tend to be more manageable
at slower response rates, as these make use of filtering, echo verification, and longer
fail-safe delay.
filter:
averages successive measurements to filter out false echoes
echo verification: discriminates between agitator blades in motion (spurious noise) and
the target surface (true echo)
fail-safe timer: establishes the period from the time a loss of echo (LOE) starts until the
fail-safe default (P071) is triggered. The P003 pre-set timer value can be overridden by
P070.
P004 Antenna
Identifies antenna configuration. [Tim: is this final?]
240
factory
241
rod + 50mm extension
242
rod + 100mm extension
Values
243
243243
243 rod + 150mm extension (50 + 100mm)
Setting this parameter automatically configures the offset correction, P652.
Horn antennas and waveguide/horn combinations will come from the factory with P652
pre-set and P004 set to 240
. [still ok?]