PL-611 IQ Radar 300 Page 55
Parameters
Parameters
Parameters
Parameters
Parameter Descriptions
The parameters are the programmable features of the IQ Radar 300. Adjust the value
settings on the parameters to configure the unit.
The parameter tables show the values you need to enter in bold type, followed by
additional information when necessary. The pre-set values are the units factory settings
that may need alteration for specific applications.
Press the PROGRAM key to access the parameter settings.
[Tim: do you want to
indicate the default values?]
P000 Lock
Secures the IQ Radar 300 from changes.
1954
Lock off: programming permitted
Value
other
Lock activated: programming secured
To access this parameter directly, press 000 and enter any value other than 1954 to
secure the programming lock. The PROGRAM mode is active for viewing only. To
unlock, access this parameter and enter 1954.
WARNING: Use this lock as backup security only. It uses a fixed value which
can be discovered by unauthorized personnel.
Quick Start Parameters (P001 to P007)
Parameters P001 to P007 are the main settings that apply to all applications and get the
system operational.
P001 Operation
Determines the mode of measurement.
1
Level: material level referenced to empty distance (P006)
2
Space: space to material level referenced from span (P007)
Values
3
Distance: distance to target referenced from the flange face
Level (a.k.a. volume)
(P001 = 1)
Space (a.k.a ullage)
(P001 = 2)
Distance
(P001 = 3)