User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
PL-611 IQ Radar 300 Page 55
Parameters
Parameters
Parameters
Parameters
Parameter Descriptions
The parameters are the programmable features of the IQ Radar 300. Adjust the value
settings on the parameters to configure the unit.
The parameter tables show the values you need to enter in bold type, followed by
additional information when necessary. The pre-set values are the unit’s factory settings
that may need alteration for specific applications.
Press the PROGRAM key to access the parameter settings.
[Tim: do you want to
indicate the default values?]
P000 Lock
Secures the IQ Radar 300 from changes.
1954
Lock off: programming permitted
Value
other
Lock activated: programming secured
To access this parameter directly, press 000 and enter any value other than 1954 to
secure the programming lock. The PROGRAM mode is active for viewing only. To
unlock, access this parameter and enter 1954.
WARNING: Use this lock as backup security only. It uses a fixed value which
can be discovered by unauthorized personnel.
Quick Start Parameters (P001 to P007)
Parameters P001 to P007 are the main settings that apply to all applications and get the
system operational.
P001 Operation
Determines the mode of measurement.
1
Level: material level referenced to empty distance (P006)
2
Space: space to material level referenced from span (P007)
Values
3
Distance: distance to target referenced from the flange face
Level (a.k.a. volume)
(P001 = 1)
Space (a.k.a ullage)
(P001 = 2)
Distance
(P001 = 3)