Applications
Applications
Applications
Applications
Note: Only set P837 if product is at least 2.5m (78) away. If closer, leave P837 at 0
00
0
until such time the level drops below 2.5m (78).
Pipe P655 Value
50mm (2) 0.827
80mm (3) 0.915
100mm (4) 0.955
150mm (6) 0.980
200mm (8) 0.990
Note:
See the P655 table on page 67 for other pipe diameters.
Run: To start normal operation, press the PROGRAM key .