User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
Page 48 IQ Radar 300 PL-611
Operation
Operation
Operation
Operation
Volume
To program the unit for volume, set:
• operation (P001) to level 1 (see page 55)
• tank shape (P050) to a value other than 0 (see page 57)
• other volume parameters (P051 to P053) as required.
To program the unit for ullage, set:
• operation (P001) to space 2 (see page 55).
Fail-Safe
When the fail-safe timer (P070) expires, the mA output responds as follows:
Fail-safe Mode (071) Status (0/4 - 20) Status (20 - 0/4)
1 = high 22 0/2
2 = low 0/2 22
3 = hold hold hold
Run/Program
When the IQ Radar 300 changes from RUN
RUNRUN
RUN to PROGRAM
PROGRAMPROGRAM
PROGRAM, the unit no longer responds to
the process. The last measurement is stored and the associated readings and mA
output are held.
The unit reverts to the parameter last addressed during the previous program session.
Upon return to RUN
RUNRUN
RUN, the transceiver resumes operation. The reading and mA output
default to the last measurement taken. The reading and associated outputs migrate to
the current process level at a rate controlled by the measurement response (P003).
If the IQ 300 is left in PROGRAM
PROGRAMPROGRAM
PROGRAM
mode for 10 minutes without input, it automatically
reverts to RUN
RUNRUN
RUN mode.