User's Manual
Table Of Contents
- Table of Contents
- General Information
- Specifications
- Installation
- Location
- Dimensions: IQ Radar 300 with Rod Antenna
- Dimensions: Threaded Rod
- Dimensions: Horn
- Mounting
- Rod Assembly
- Mounting: Rod Assembly
- Mounting: Manhole Covers
- Mounting: Horn Antennas
- Mounting: Waveguide Antenna
- Mounting: Stillpipe or Sidepipe
- Mounting: Horn with Waveguide Extensions
- Mounting: Sanitary Mounting
- Mounting: Location
- Interconnection
- Start Up
- Operation(
- Application Examples
- Parameter Descriptions
- _
- _
- Quick Start Parameters (P001 to P007)
- Volume Parameters (P050 to P053)
- Display and Reading Parameters (P060 to P063)
- Fail-Safe Parameters (P070 to P072)
- mA Parameters (P200 to P219)
- Independent mA Setpoints Parameters (P210 and P211)
- Profile Record Parameters (P330 to P337)
- Auto Record ON and OFF Setpoint Parameters (P334 to P337)
- Installation Records Parameter
- Range Calibration Parameters
- Rate Parameters
- Measurement Verification Parameters
- Communication Parameters
- Echo Processing Parameters
- Algorithm Parameters
- TVT Adjustment Parameters
- P837 Auto Near TVT
- Test Parameters
- _
- Communications: Modbus Register Map
- Communications: Data Types
- Error Handling
- Troubleshooting
- Maintenance(
- Appendix I
- Appendix II
- Appendix III
- Appendix IV
- Appendix V
Page 30 IQ Radar 300 PL-611
Installation
Installation
Installation
Installation
Mounting: Stillpipe or Sidepipe
An alternate to the waveguide antenna, this option is also used for products with an ε
r
less than 3 or for extremely turbulent or vortex conditions. This mounting arrangement
can also be used to provide optimum signal conditions on foaming materials.
Suitable pipe diameters are 2” (50mm) to 10” (250mm). A rod antenna or a horn antenna
may be used.
Note:
: :
: The measurement range is reduced to 13m (43’) for a 50mm (2”) stillpipe or
14.5m (47’) for an 80mm (3”) stillpipe.
Smoothness
One continuous length of metallic pipe is preferred (no joints). If long length dictates the
need for joints, then you must machine the joints to close tolerances (± 0.25mm [±
0.010”]) and weld a connecting sleeve on the outside.
See P655 on page 67.
Ensure there is a vent at the upper end of the surge pipe to equalize pressure and keep
the liquid level in the pipe constant with level in the vessel.
vent hole
Suitable pipe diameters are 2” (50mm) to
10” (250mm).
You can use either a Rod or Horn
antenna.