PARAMETER DESCRIPTION _
P820 algorithm
Selects the algorithm to be applied to the echo profile in order to extract
the true echo.
entry: 1 = best of first and largest
2 = first echo
3 = largest echo
P830 TVT type
Selects the TVT profile applied to the echo profile.
entry: 1 = standard
2 = flat
P900 software revision
Displays the EPROM software revision level.
P901 memory
Tests the memory. Test is initiated by scrolling to the parameter or
repeated by
display: PASS = normal
FAIL = consult Milltronics
P911 mA output value
Displays the value from the previous measurement. A test value can be
entered and the displayed value is transmitted to the output. Upon
returning to the run mode, the parameter assumes the actual mA output
level.
P920 reading measurement
Displays the reading measurement that the unit is programmed for in
run mode (P001, operation).
P921 material measurement
Displays the reading measurement as though the unit were
programmed to read level (P001 = 1).
P922 space measurement
Displays the reading measurement as though the unit were
programmed to read space (P001 = 2).