User's Manual

PL-550 38
PARAMETER DESCRIPTION
P341 run time
View the accumulated number of days the IQ Radar 160 has been
operating.
P652 offset correction
An offset value can be applied to the reading as a correction
to the measurement.
values: -999 to 9999
P800 near blanking
Sets the amount of blanking as measured from the flange face and
extending into the measurement range. Refer to Operation /
Blanking.
enter value in units of P005.
P801 range extension
Sets the amount of range extension as measured from the empty
distance (P006) and extending into the far end blanking. Refer to
Operation / Blanking.
enter as a % of P006, the distance below empty not blanked.
P804 confidence threshold
The minimum echo confidence in dB that the echo must meet in order
to prevent a loss of echo condition and the expiration of the fail-safe
timer (P070).
enter value in the range of 0 to 99.
P805 echo confidence
A measure of echo reliability.
P806 echo strength
The absolute strength of the selected echo, in dB above 1 ยตV rms.