PARAMETER DESCRIPTION _
PARAMETER DESCRIPTION
P000 lock
Locks out the ability to change parameter values P001 through P999.
The program mode is still active, but restricted to viewing only. The lock
is enabled if P000 value is other than 1954.
entry: 1954 = unlocked
1954 = locked
P001 operation
Determines the mode of measurement.
entry: 1 = level; material level referenced to empty
distance (P006)
2 = space; space to material level referenced
from zerospan
3 = distance; distance to target referenced
from the flange face
Level Space Distance
(P001 = 1) (P001 = 2) (P001 = 3)