APPLICATION EXAMPLE
The minimum distance from the antenna face to the target
is limited by the near blanking, P800.
The application is to obtain a level measurement and corresponding 4-20 mA
output proportional to material levels in a chemical tank. The antenna flange is
5 m from the tank bottom. The empty level is 0 m (bottom) and the full level
(span) is 4.5 m from the bottom. The maximum rate of filling or emptying is about
1 m/min. In the event of a loss of echo, the IQ Radar 160 is to go into fail-safe low
after 2 minutes.
reset:
P999 master reset
program:
P001 enter ‘1’ mode of measurement = level
P002 enter ‘1’ material = liquid
P003 enter ‘2’ measurement response = 1m/min.
P004 enter ‘240’ antenna = dielectric rod, standard length
P005 enter ‘1’ units = metres
P006 enter ‘5’ empty distance = 5 m
P007 enter ‘4.5’ span = 4.5 m
P070 enter ‘2’ fail-safe timer = 2 min.
P071 enter ‘2’ fail-safe = low
run:
press run to start normal operation
Empty
(P006)
Span
(P007)