Operating instructions
J. BURNER MOTOR FAILS TO START
1. Check burner switch on side of burner.
Up is “on” may be defective
2. Water temperature control stuck “open.”
Jumper wire terminals on temp switch momentarily. If burner starts, replace
temperature switch.
3. Defective flow switch.
Jumper wire terminals on flow switch momentarily. If burner starts, replace
flow switch.
4. Overload button tripped on burner motor.
Depress button to reset. If problem continues, consult electrician.
K. BURNER MOTOR FAILS TO STOP
1. Check burner switch.
Down is “off” may be defective.
2. Water temperature control stuck “closed.”
Disconnect one wire of the temperature control switch to see if control is the
problem.
L. BURNER FAILS TO IGNITE
1. Empty or low fuel supply.
Replenish fuel supply.
2. Plugged filter or nozzle.
Replace filter cartridge and appropriate nozzle.
3. Air leaks or air in oil line.
Bleed pump. Check oil line fittings for air leaks.
4. Weak ignitor/transformer.
With an insulated screwdriver, draw a spark across the ignitors,
spark should be ¾” to 1”. At ½” replace ignitor transformer.
TROUBLESHOOTING (CONTINUED)
26