Datasheet
A
B
C
D
E
F
H
I
J
K
L
M
N
O
P
Q
R
S
T
UE43-3MF2D3 | UE43-3MF
SAFETY RELAYS
Illustration may differ
Ordering information
Type Part no.
UE43-3MF2D3 6024897
Other models and accessories www.sick.com/UE43-3MF
Detailed technical data
Safety-related parameters
Safety integrity level
SIL3 (IEC61508)
SILCL3 (EN62061)
Category
Category 4(ENISO13849)
Performance level
PLe(ENISO13849)
B
10d
parameter
1x10
6
switching cycles (AC-15, 230V, I= 0.5A)
3.5x10
5
switching cycles (DC-13, 24V, I= 2A)
1.2x10
6
switching cycles (DC-13, 24V, I= 0.5A)
PFH
D
(mean probability of a dangerous fail-
ure per hour)
3.0x10
-8
(ENISO13849)
T
M
(mission time)
20years (ENISO13849)
Stop category
0(EN60204-1)
Interfaces
Connection type
Fixed screw terminals
Number of enable current (N/O) contacts
3, relevant for safety
Electrical data
Operating data
Voltage supply
A1, A2
Output circuit > 25VAC / 60VDC PELV
Output circuit ≤ 25VAC / 60VDC PELV or SELV
Supply voltage V
s
A1, A2
24VDC (20.4VDC... 26.4VDC)
Residual ripple
(≤ 2.4V
pp
)
1)
Power consumption
(≤ 1W (DC))
1)
In DC operation, within the limits of V
S
.
2 SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK Online data sheet | 2018-11-26 12:21:14
Subject to change without notice