Datasheet
UE410-4RO3 | Flexi Classic
SAFETY CONTROLLERS
Input voltage 18VDC... 30VDC
Enable current contacts
Terminals 13/14, 23/24, 33/34, 43/44
Type of output Potential-free NO contacts, positively guided
Switching voltage 5VAC/DC... 253VAC/DC
Current-carrying capacity per OSSD 10mA... 6A
Signalling current contacts
Terminals Y14, Y24
Type of output NO contact, connected to internal 24VDC, positively guided, current-limited
Output voltage 16VDC... 30VDC
Output current ≤75mA
Contactor monitoring contacts
Terminals Y1/Y2, Y3/Y4
Type of output Potential-free NC contacts, positively guided
Switching voltage 5VAC/DC... 253VAC/DC
Current-carrying capacity per OSSD 10mA... 6A
1)
Via FLEXBUS+.
Mechanical data
Dimensions (Wx Hx D)
22.5mmx 96.5mmx 120.8mm
Weight
186g (± 5%)
Ambient data
Enclosure rating
Housing IP40 (EN60529)
Terminals IP20 (EN60529)
Ambient operating temperature
–25°C... +55°C
Storage temperature
–25°C... +70°C
Air humidity
15%... 95%, Non-condensing
Climate conditions according to
EN61131-2 (55°C ambient operating temperature, 95% rel. humidity)
Electromagnetic compatibility (EMC)
Class A (EN61000-6-2, EN55011)
Vibration resistance
5g RMS, 5Hz... 500Hz (EN60068-2-64)
Classifications
ECl@ss 5.0
27242290
ECl@ss 5.1.4
27249090
ECl@ss 6.0
27249090
ECl@ss 6.2
27249090
ECl@ss 7.0
27249090
ECl@ss 8.0
27249090
ECl@ss 8.1
27249090
ECl@ss 9.0
27249090
ETIM 5.0
EC002632
ETIM 6.0
EC002632
2018-09-17 16:53:32 | Online data sheet
Subject to change without notice
SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK 3