Datasheet
A
B
C
D
E
F
H
I
J
K
L
M
N
O
P
Q
R
S
T
UE10-4XT3D2 | UE10-4XT
SAFETY RELAYS
Illustration may differ
Ordering information
Type Part no.
UE10-4XT3D2 6024920
Other models and accessories www.sick.com/UE10-4XT
Detailed technical data
Safety-related parameters
Safety integrity level
SIL3 (IEC61508)
1)
SILCL3 (EN62061)
1)
Category
Category 4(ENISO13849)
1)
Performance level
PLe(ENISO13849)
1)
B
10d
parameter
2.5x10
6
witching cycles (AC-15, 230V, I= 1.5A)
6x10
6
switching cycles (AC-15, 230V, I= 0.75A)
2x10
6
switching cycles (DC-13, 24V, I= 2.5A)
10x10
6
switching cycles (DC-13, 24V, I= 0.6A)
PFH
D
(mean probability of a dangerous fail-
ure per hour)
2.47x10
-8
(ENISO13849)
T
M
(mission time)
20years (ENISO13849)
1)
If the feedback current path Y1 - Y2 (external device monitoring) is monitored using an appropriate main unit.
Interfaces
Connection type
Plug-in screw-type terminals
Number of enable current (N/O) contacts
4, relevant for safety
Electrical data
Operating data
Voltage supply
A1, A2
Output circuit > 25VAC / 60VDC PELV
Output circuit ≤ 25VAC / 60VDC PELV or SELV
Supply voltage V
S
A1, A2
24VAC/DC (20.4VAC/DC... 26.4VAC/DC)
Residual ripple
(≤ 2.4V
pp
)
1)
1)
In DC operation, within the limits of V
S
.
2 SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK Online data sheet | 2018-09-11 15:13:28
Subject to change without notice