Installation Guide
FUNCTIONSELECTORJUMPERSETTINGS:
J1 MASTERSWITCH
1-2Latching
2-3Momentary
Factorysettingis1-2forallfourJumpers
OPERATION
EverytimethepositionoftheREMOTESWITCHchanges,theMotorizedValve(s)rotate
to the opposite position. In addition, if connected, the heater thermostat setting changes
fromLOWtoHIGHorHIGHtoLOW.
TROUBLE SHOOTING
Problem Cause Solution
1.Nothingworks. a.Nopowertotransformer Checkpowersupply
b.120Voltisconnectedto Connect120VoltsupplytoBlack
240Voltleads andWhiteleads
c.240Voltwasconnectedto Replacedefectivecontrolunit
120Volttransformerleads.
2.Remoteinstalled a.JumperJ1isonpins2-3 PlaceJumperJ1onPins1-2
ActuatorSwitchwill ormissing.
not operate
equipment.
3.Wiredremoteis a.Connectorisincorrectly Re-attach8-pinconnector
not working attached
b.Corroded/dirtyconnector Cleanconnectorpins.
pins
4.Valveactuators a.Actuatorsareout-of-sync Synchronizeactuators(Referto
workopposite valveactuatormanual)
pump relay
3