Specifications
Site Requirements and Preparation
13 – 4 ShoreTel, Inc.
Input Power
For backup purposes, ShoreTel recommends that all ShoreGear voice switches and the
ShoreWare server be connected to an uninterruptable power supply (UPS). This
ensures that telephone service will continue in the event of a power interruption.
Table 13-2 shows the power requirements for the ShoreGear voice switches.
Power and Heat Dissipation
The voice switches dissipate power and heat. ShoreTel recommends that you use the
information provided in Table 13-3 to help calculate the ventilation requirements of the
equipment room.
Environmental Requirements
The ShoreGear voice switches require that the environmental specifications provided in
Table 13-4 be met.
Table 13-2 ShoreGear Voice Switch Power Input
Parameter ShoreGear-120/24 ShoreGear-60/12 ShoreGear-40/8 ShoreGear-T1 ShoreGear-E1
Input voltage 100–240 VAC
50–60 Hz
100–240 VAC
50–60 Hz
100–240 VAC
50–60 Hz
100–240 VAC
50–60 Hz
100–240 VAC
50–60 Hz
Current
consumption
@110 VAC
(maximum)
2A max 2A max 1A max 1A max 1A max
Number of
grounded
110 VAC outlets
per switch
1 1111
Power
consumption
(typical)
90W typ 90W typ 50W typ 50W typ 50W typ
Table 13-3 ShoreGear Voice Switch Power and Heat Dissipation
Parameter ShoreGear-120/24 ShoreGear-60/12 ShoreGear-40/8 ShoreGear-T1 ShoreGear-E1
Power
dissipation
(typical)
90 W typ 90 W typ 50 W typ 50 W typ 50 W typ
Heat dissipation 215 BTU/hour 140 BTU/hour 85 BTU/hour 62 BTU/hour 62 BTU/hour
Table 13-4 ShoreGear Environmental Specifications
Parameter Specification
Operating temperature 0° to 50° C (32° to 122° F)
Operating humidity (non-condensing) 10% to 90%
Storage temperature –30° C to 70° C (-34.4° to 158° F)