Instruction manual
6
1.2 Rated input
(Table 1.2-1)
Input type Input range Resolution
-200 to 1370 -320 to 2500 1 ( )
K
-199.9 to 400.0 -199.9 to 750.0 0.1 ( )
J
-200 to 1000 -320 to 1800 1 ( )
R 0 to 1760 0 to 3200 1 ( )
S 0 to 1760 0 to 3200 1 ( )
B 0 to 1820 0 to 3300 1 ( )
E
-200 to 800 -320 to 1500 1 ( )
T -199.9 to 400.0 -199.9 to 750.0 0.1 ( )
N -200 to 1300 -320 to 2300 1 ( )
PL- 0 to 1390 0 to 2500 1 ( )
Thermo-
couple
C (W/Re5-26) 0 to 2315 0 to 4200 1 ( )
-199.9 to 850.0 -199.9 to 999.9 0.1 ( )
Pt100
-200 to 850 -300 to 1500 1 ( )
-199.9 to 500.0 -199.9 to 900.0 0.1 ( )
RTD
JPt100
-200 to 500 -300 to 900 1 ( )
4 to 20mA DC -1999 to 9999 *1, *2 1
0 to 20mA DC -1999 to 9999 *1, *2 1
0 to 1V DC
-1999 to 9999 *1 1
0 to 5V DC
-1999 to 9999 *1 1
1 to 5V DC -1999 to 9999 *1 1
DC
current
DC
voltage
0 to 10V DC -1999 to 9999 *1 1
(*1) For DC current and voltage inputs, scaling and decimal point place are changeable.
(*2) For DC current input, 50 shunt resistor (sold separately) must be connected.
1.3 How to read the model label
Warning
Do not take the inner assembly out or touch the terminal with the power supply
ON when confirming the model label.
Touching the terminal with the power switched ON may result in severe injury
or death due to Electric Shock.
Model labels are attached to the case and the left side of the inner assembly.
[Example]
(Fig. 1.3-1) Case label
Model
Serial number
(Fig. 1.3-2) Inner assembly label