Instruction manual

57
Problem Presumed cause and solution
The setting indication
does not change in the
input range even if the
, keys are
pressed, and new
values are unable to
be set.
• SV high limit or low limit in Auxiliary function setting mode 1
may be set at the point where the value does not change.
Set it to a suitable value ( , or ) while in
Auxiliary function setting mode 1. (p.31)
<Control>
Problem Presumed cause and solution
If process variable
(temperature) does
not rise.
Thermocouple or RTD is burnt out.
• Lead wire of thermocouple or RTD is not securely
connected to the instrument terminals.
• Direct (Cooling) action [ ] has been selected during
the Direct/Reverse action selection [ ] in “5. Setup”.
Select Reverse (Heating) [ ] action. (p.20)
If the control output
(OUT) remains in an
ON status.
• OUT low limit value is set to 100% or higher in Auxiliary
function setting mode 2. (p.17)
The proportional band may be set at an extremely small
value.
Set it to a suitable value. (p.28)
If the control output
(OUT) remains in an
OFF status.
• OUT high limit value is set to 0% or less in Auxiliary function
setting mode 2. (p.17)
The proportional band may be set at an extremely high
value.
Set it to a suitable value. (p.28)
Step numbers progress
fast and program
control stops soon after
it has started.
The program has not been set.
Set the program from the Pattern (Step SV/Time) setting
mode. (pages 25, 26)
The default value is PV start.
If the PV is higher than the Step SV, the program advances
and it ends soon. (p.17)
The step does not
proceed.
Wait function is working.
Release the wait function.
The fixed value control is performing due to Hold function.
Press the RUN Key for more than 1 second to release
the Hold function. (p.39)
For all other malfunctions, please contact our main office or dealers.