Instruction manual
54
Circuit insulation configuration
When the control output (OUT) is non-contact voltage or DC current,
A is not electrically insulated from B, and A is not electrically insulated from C.
Insulation resistance
10M or more, at 500V DC for other combinations except those mentioned above.
Dielectric strength
Between input terminal and ground terminal, 1.5kV AC for 1 minute
Between input terminal and power terminal, 1.5kV AC for 1 minute
Between output terminal and ground terminal, 1.5kV AC for 1 minute
Between output terminal and power terminal, 1.5kV AC for 1 minute
Between power terminal and ground terminal, 1.5kV AC for 1 minute
Weight : Approx. 370g
External dimensions: 96 x 96 x 100mm (W x H x D)
Material : Case, Flame-resistant resin
Color : Case, Light gray
Attached functions : Set value lock, Sensor correction, Power failure countermeasure,
Self-diagnosis, Automatic cold junction temperature
compensation, Burnout (overscale), Input error, Warm-up
indication
Accessories : Mounting brackets 1 set
Instruction manual 1 copy
Terminal cover 2 pieces (When the TC option is added.)
10.2 Optional specifications
Serial communication (Option code: C5)
External operation function cannot be used if C5 option is added.
The following operations can be executed from an external computer.
(1) Reading and setting of Step SV, Step time, PID values and various set values
(2) Reading of the PV and the action status
(3) Function change
Alarm 2 (A2) output or
Insulated power output (P24)