Instruction manual

38
[Indication during Time signal action]
If Time signal output is selected during the [Event output function selection], Event
output is turned on during time signal output ON time.
Time signal output ON time follows time signal output OFF time after the program
control starts.
If Time signal output ON time has elapsed, Event output is turned off.
The following shows the indication during time signal action.
PTN display : Selected program pattern number
PV display : Current actual temperature
STEP display : Step number of the program
control which is running.
SV display : Current step SV
RUN indicator : Lit during program control run
EVT indicator : Lit during Time signal output ON
Other indicators: Lit or unlit according to the
controller status
[Indication during Pattern end output]
If Pattern end output is selected during the Event output function selection, Event
output is turned on for the time which has been set during the Pattern end output
time setting.
If Pattern end output time has elapsed, Event output is turned off.
If Pattern end output time is set to 0, the output remains ON.
By pressing the Key for 1 second or longer, the pattern end output is turned
off, and the controller reverts to the Program standby mode.
The following shows the indication during pattern end output.
PTN display : Selected program pattern number
PV display : Current actual temperature
STEP display : Unlit
SV display : flashes while pattern
end output is on.
RUN indicator : Unlit
EVT indicator : Lit while pattern end output is ON
Other indicators: Unlit
[Indication during Run output]
If Run output is selected during the Event output function selection, Event output is
turned on during program control run.
When the program control ends or when making program control stop by pressing
the Key for 1 second or longer, Event output is turned off.
PTN PV
Actual temp.
STEP SV
Step SV
PTN PV
Actual temp.
STEP SV
Flashes while Pattern end
output is ON.