Instruction manual

32
Communication protocol
Selects the communication protocol.
Available only when C5/SVTC (option) is added.
Selecting item:
Shinko protocol
Set value digital transmission (Shinko
protocol)
Set value digital reception (Shinko
protocol)
Modbus protocol ASCII mode
Modbus protocol RTU mode
Default value: Shinko protocol
Instrument number
Selects the instrument number.
Set the instrument number of the PCD-33A
individually when communicating by
connecting plural PCD-33A units.
Available only when C5/SVTC (option) is added.
Setting range: 0 to 95
Default value: 0
Communication speed
Selects the communication speed.
Available only when C5/SVTC (option) is added.
Selecting item: 2400bps
4800bps
9600bps
19200bps
Default value: 9600bps
Parity
Selects the parity type from a choice of: No parity,
Even and Odd parity in accordance with the host
computer.
Available when C5/SVTC (option) is added, and
when Modbus ASCII or RTU mode is selected.
Selecting item: No parity
Even parity
Odd parity
Default value: Even parity
Stop bit
Selects the stop bit in accordance with the host
computer from 1 or 2.
Available when C5/SVTC (option) is added, and
when Modbus ASCII or RTU mode is selected.
Selecting item: (stop bit 1)
(stop bit 2)
Default value: (stop bit 1)