Instruction manual
31
[Program standby mode or Program control run mode]
(8) Auxiliary function setting mode 1
Settings/Selections in Auxiliary function setting mode 1 are common to all program
pattern numbers.
[Program standby mode or Program control run mode]
Press the Key for 3 seconds while holding
down the key.
Auxiliary function setting mode 1 appears, and
+ (3 sec) Set value lock selection item is indicated.
[Auxiliary function setting mode 1]
Set value lock
Locks the set value to prevent setting errors.
Before selecting the lock function, set each
setting item in advance.
Unlock: All set values can be changed.
Lock : None of the set values can be changed.
• Selecting item: (Unlock)
(Lock)
• Default value: (Unlock)
SV high limit
Sets the step SV high limit.
• Setting range:
SV low limit to input range high limit value
DC input: SV low limit to scaling high limit value
• Default value: 1370
SV low limit
Sets the step SV low limit.
• Setting range:
Input range low limit value to SV high limit
DC input: scaling low limit value to
SV high limit
• Default value: -200
Sensor correction
Sets the value to correct PV.
PV after sensor correction= Current PV+ Sensor
correction value
• Setting range: -100.0 to 100.0 ( )
DC input: -1000 to 1000 (The placement of
the decimal point place follows the selection.)
• Default value: 0.0