Instruction manual
30
[Program standby mode or Program control run mode]
Press the key for 3 seconds while
holding down the key.
Wait parameter setting mode appears, and
+ (3 sec) Wait value setting item is indicated.
[Wait parameter setting mode]
Wait value
Sets Pattern 1 Wait value.
The step of which temperature is rising:
Step SV – Wait value
The step of which temperature is falling:
Step SV + Wait value
Wait action is disabled when set to 0 or 0.0.
• Setting range: (0 to 100) ( )
For the input with a decimal point:
(0.0 to 100.0) ( )
For DC input: (0 to 1000)(The placement
of the decimal point follows the selection.)
• Default value: 0 ( )
Step 1 Wait function
Selects Step 1 Wait function Used or Not used.
Not available if Wait value is set to 0 or 0.0 ( )
during Wait value setting.
• Selecting item:
: Wait function Not used
: Wait function Used
• Default value:
: Wait function Not used
Step 2 Wait function
Selects Step 2 Wait function Used or Not used.
Not available if Wait value is set to 0 or 0.0 ( )
during Wait value setting.
• Selecting item:
: Wait function Not used
: Wait function Used
• Default value:
: Wait function Not used
Step 9 Wait function
Selects Step 9 Wait function Used or Not used.
Not available if Wait value is set to 0 or 0.0 ( )
during Wait value setting.
• Selecting item:
: Wait function Not used
: Wait function Used
• Default value:
: WAIT function Not used