Instruction manual
28
Pattern 1 Time signal output OFF time
Sets Time signal output OFF time after running
program control.
Available only when Time signal output is
selected during Event output function selection.
• Setting range: 00:00 to 99.59
(Hour:Minute or Minute:Second)
• Default value: 00:00 (Hour:Minute)
Pattern 1 Time signal output ON time
Sets Time signal output ON time following the
Time signal output OFF time.
Available only when Time signal output is
selected during Event output function selection.
• Setting range: 00:00 to 99.59
(Hour:Minute or Minute:Second)
• Default value: 00:00 (Hour:Minute)
[Program standby mode or Program control run mode]
(6) PID parameter setting mode
Sets parameters and items necessary for the control such as AT Perform/Cancel,
P, I, D and Proportional cycle, etc.
Settings in this mode are common to all program pattern numbers.
[Program standby mode or Program control run mode]
Press the Key while holding down the
key.
PID parameter setting mode appears, and
+ AT Perform/Cancel is indicated.
[PID parameter setting mode]
AT Perform/Cancel
Selects Auto-tuning Perform or Cancel.
Available only during program control run
and during PID control.
Not available for Program standby mode.
• Setting range: AT Cancel
AT Perform
• Default value: AT Cancel
Proportional band
Sets the proportional band for the control output.
ON/OFF control when set to 0 or 0.0.
• Setting range: 0 to 1000 (0 to 2000 )
For the input with a decimal point,
0.0 to 999.9 (0 to 999.9 )
For DC input, 0.0 to 100.0%
• Default value: 10
PTN PV
STEP SV
PTN PV
STEP SV
PTN PV
Actual temp.
STEP SV
PTN PV
Actual temp.
STEP SV
PTN PV
STEP SV
PTN PV
STEP SV