[Run output] (Fig. 5.3-3)
This is outputted during the program control. (Fig. 5.3-3)
(Fig. 5.3-3)
(21) Pattern end output time
Sets pattern end output time after pattern end output has been selected during
Event output function selection.
When 0 seconds are set, the output remains ON until the Key is pressed.
Available only when pattern end output is selected during Event output function
selection.
• Setting range: 0 to 9999 seconds
• Default value: 0 seconds
(22) Direct/Reverse control action
Selects the Direct (Cooling) or Reverse (Heating) control action.
Direct control action
When PV (process variable) is higher than SV (desired value), the control output
(OUT) is turned ON. This is a direct control action.
This is used for cooling control for devices such as refrigerators.
Reverse control action
When PV (process variable) is lower than SV (desired value), the control output
(OUT) is turned ON. This is a reverse control action.
This is used for heating control for devices such as electric furnaces.
• Selecting item: Reverse (Heating) control action
Direct (cooling) control action
• Default value: Reverse (Heating) control action
Temperature
Step 1
Step 2 Step 3
C
Time
Program control end
Run output OFF
Run output OFF
Run output ON