(12) Alarm 1 (A1) type
Selects Alarm 1 (A1) type, referring to 8.5 Alarm 1 (A1) action (pages 48, 49).
Note: If an alarm type is changed, the alarm set value becomes 0 (0.0).
• Selecting item: No alarm action
High limit alarm
Low limit alarm
High and Low limits alarm
High and Low limit range alarm
Process High alarm
Process Low alarm
High limit alarm with standby
Low limit alarm with standby
High and Low limits alarm with standby
• Default value: No alarm action
(13) Alarm 2 (A2) type
Selects Alarm 2 (A2) type, referring to 8.5 Alarm 2 (A2) action (pages 48, 49).
Note: If an alarm type is changed, the alarm set value becomes 0 (0.0).
The selecting items and default value are the same as those of Alarm 1 (A1) type.
Not available if P24 (option) is added.
(14) Alarm 1 (A1) Energized/De-energized
Selects Alarm 1 (A1) Energized/De-energized.
Not available if No alarm action is selected during Alarm 1 (A1) type selection.
• Selecting item: Energized, De-energized
• Default value: Energized
(15) Alarm 2 (A2) Energized/De-energized
Selects Alarm 2 (A2) Energized/De-energized.
Not available if No alarm action is selected during Alarm 2 (A2) type selection.
Not available if P24 (option) is added.
The selecting item and default value are the same as those of Alarm 1 (A1)
Energized/De-energized selection.
(16) Alarm 1 (A1) hysteresis
Sets Alarm 1 (A1) hysteresis.
Not available if No alarm action is selected during Alarm 1 (A1) type selection.
• Setting range: 0.1 to 100.0 ( )
DC input: 1 to 1000 (The placement of the decimal point follows the selection.)
• Default value: 1.0
(17) Alarm 2 (A2) hysteresis
Sets Alarm 2 (A2) hysteresis.
Not available if No alarm action is selected during Alarm 2 (A2) type selection.
Not available if P24 (option) is added.
The setting range and default value are the same as those of Alarm 1 (A1) hysteresis
setting.
(18) Alarm 1 (A1) action delay timer
Sets Alarm 1 (A1) action delay timer.
Not available if No alarm action is selected during Alarm 1 (A1) type selection.
• Setting range: 0 to 9999 seconds
• Default value: 0 seconds
(19) Alarm 2 (A2) action delay timer
Sets Alarm 2 (A2) action delay timer.
Not available if No alarm action is selected during Alarm 2 (A2) type selection.
Not available if P24 (option) is added.
The setting range and default value are the same as those of Alarm 1 (A1) action
delay timer setting.