Instruction manual

16
5.3 Setting items in Auxiliary function setting mode 2
(1) : Input type
Selects a sensor type and temperature unit.
When changing the input from DC voltage to other inputs, remove the sensor
connected to this controller, then change the input. If the input is changed while
the sensor is connected, the input circuit may break.
Set the same sensor type as the users’.
Selecting item: Refer to (Table 5.3-1) below.
Default value: (K, -200 to 1370 )
(Table 5.3-1)
Input Input range
Character
Input range
Character
-200 to 1370 -320 to 2500
K
-199.9 to 400.0 -199.9 to 750.0
J
-200 to 1000 -320 to 1800
R
0 to 1760 0 to 3200
S
0 to 1760 0 to 3200
B
0 to 1820 0 to 3300
E
-200 to 800 -320 to 1500
T
-199.9 to 400.0 -199.9 to 750.0
N
-200 to 1300 -320 to 2300
PL-
0 to 1390 0 to 2500
Thermo-
couple
C(W/Re5-26)
0 to 2315 0 to 4200
Pt100
-199.9 to 850.0 -199.9 to 999.9
JPt100
-199.9 to 500.0 -199.9 to 900.0
Pt100
-200 to 850 -300 to 1500
RTD
JPt100
-200 to 500 -300 to 900
4 to 20mA
-1999 to 9999
0 to 20mA
-1999 to 9999
0 to 1V
-1999 to 9999
0 to 5V
-1999 to 9999
1 to 5V
-1999 to 9999
DC
current
DC
voltage
0 to 10V
-1999 to 9999
(2) Scaling high limit
Available only for DC current and voltage input
• Setting range: Scaling low limit value to input range high limit value
• Default value: 9999
(3) Scaling low limit
Available only for DC current and voltage input
• Setting range: Input range low limit value to scaling high limit value
• Default value: -1999
(4) Decimal point place
For DC current and voltage input, the input indication can be freely set.
(e.g.) If DC voltage input 0 to 1V DC is set, 0V corresponds to –1999, and 1V
corresponds to 9999. To indicate 0V as 0.0 and 1V as 100.0, Scaling high limit
is1000, Scaling low limit is 0, and select the decimal point place as “1 digit after
the decimal point ( )”.